gaSteam runs on natural gas or LPG, and is fitted with a sophisticated built-in electronic controller that can also manage other types of gas by simply setting a number of burner calibration parameters.
CAREL’s extensive experience in the humidification sector has led to the development of gaSteam, the range of gas-fired humidifiers, available in 45, 90 and 180 kg/h models.
The exclusive design of the heat exchanger ensures very high efficiency (94-96%) and easy maintenance. Made from stainless steel, it guarantees long life even in heavy-duty operation. The price gap between gas and electricity makes gaSteam the ideal choice for more high load applications, where steam is required many hours a day, allowing savings in the thousands of euro per year. Continuous modulation of steam flow-rate means the appliance is also suitable for precision applications. gaSteam can operate on drinkable mains water or demineralised water (R.O.). Easy to install, it features a room-sealed combustion chamber with premix burner, and gas valve with double mechanical closing; furthermore, it is fitted with multiple safety devices and comes with ETL and CE certification (issued by TÜV-DVGW).
Caracteristics
Continuous modulation from 25 to 100% (12.5% for the 180 kg/h model)
Precision: ± 2% RH
Pre-mix, room-sealed burner with forced ventilation
Air/gas control valve with double safety closing
Stainless steel boiler and heat exchanger
Pre-heating function for a faster response
Supply with mains water or demineralised water. The controller can be set for use with softened water, within the limits described in the reference tables
Frost protection function
Temperature sensor in the flue gas outlet that checks for malfunctions, and provides early warning of excessive scale on the heat exchanger
Flame detector in the burner that closes the gas valve in the event of malfunctions
Patented AFS antifoam system with corresponding sensor
Multi-stage water level sensor
Automatic water drain after 3 days of inactivity